Extreme Networks Consolidated Hardware Guide 2-5
Meeting Site Requirements
Wiring Closet Considerations
You should consider the following recommendations for your wiring closet:
Ensure that your system is easily accessible for installation and service. See Rack
Specifications and Recommendations on page 2-12 for specific recommendations.
Use AC power, 15-amp service receptacles, type N5/15 or NEMA 5-15R for 120 VAC.
Use 30 A at -40 VDC (or equivalent power between -40 and -70 VDC) for Alpine DC
power supplies. For Alpine DC power and ground cables, use 8 AWG,
high-strand-count wire cable (Alpine 3808) or 10 AWG, high-strand-count wire cable
(Alpine 3804).
Use AC power, 20 A service receptacle, NEMA L5-20R for BlackDiamond 110 VAC
power supplies.
Use AC power, 20 A service receptacle, NEMA L6-20R for BlackDiamond 220 VAC
power supplies.
Use 55 A service for BlackDiamond DC power supplies. For BlackDiamond DC
power cables, use 4 AWG, high-strand-count wire cable.
Use a vinyl floor covering in your wiring closet. (Concrete floors accumulate dust,
and carpets can cause static electricity.)
Prevent unauthorized access to wiring closets by providing door locks.
Provide adequate overhead lighting for easy maintenance.
Ensure that each wiring closet has a suitable ground. All distribution racks and
equipment installed in the closet should be grounded.
Ensure that all system environmental requirements are met, such as ambient
temperature and humidity.
Note: Extreme Networks recommends that you consult an electrical contractor
for commercial building and wiring specifications.
Temperature. Extreme Networks equipment generates a significant amount of heat. It
is essential that you provide a temperature-controlled environment for both
performance and safety.
The following are some general thermal recommendations for your wiring closet:
Ensure that the ventilation in the wiring closet is adequate to maintain a temperature
below 104° F (40° C).
Install a reliable air conditioning and ventilation system.